Passive House requirements
    For a building to be considered a Passive House, it must meet the following criteria ( for detailed criteria, please see the building certification section):
1. The Space Heating Energy Demand is not to exceed 15 kWh per square meter of net living space (treated floor area) per year or 10 W per square meter peak demand.
In climates where active cooling is needed, the Space Cooling Energy Demand requirement roughly matches the heat demand requirements above, with an additional allowance for dehumidification.
2. The Renewable Renewable Primary Energy Demand (PER, according to PHI method), the total energy to be used for all domestic applications (heating, hot water and domestic electricity) must not exceed 60 kWh per square meter of treated floor area per year for Passive House Classic. .
3. In terms of Airtightness,  a maximum of  0.6 air changes per hour at 50 Pascals pressure (ACH50), as verified with an onsite pressure test (in both pressurized and depressurized states).
    
4. Thermal comfort must be met for all living areas during winter as well as in summer, with not more than 10 % of the hours in a given year over 25 °C. For a complete overview of general quality requirements (soft criteria) see Passipedia.
Passive House buildings are planned, optimised and verified with the Passive House Planning Package (PHPP).
All of the above criteria are achieved through intelligent design and implementation of the 5 Passive House principles: thermal bridge free design, superior windows, ventilation with heat recovery, quality insulation and airtight construction.
The following five basic principles apply for the construction of Passive Houses:
Thermal insulation
All opaque building components of the exterior envelope of the house must be very   well-insulated. For most cool-termperate climates, this means a heat transfer coefficient (U-value) of 0.15  W/(m²K) at the most, i.e. a maximum of 0.15 watts per degree of temperature  difference and per square metre of exterior surface are lost.
Passive House windows
      The window frames must be well insulated and fitted with  low-e glazings filled with argon or krypton to prevent heat transfer. For most cool-termperate climates, this means a  U-value of 0.80 W/(m²K) or less, with g-values around 50% (g-value= total solar  transmittance, proportion of the solar energy available for the room).
      Ventilation heat recovery
      Efficient heat recovery ventilation is key, allowing for  a good  indoor air quality and  saving energy. In Passive House, at least 75% of the heat from the exhaust air is transferred to  the fresh air again by means of a heat exchanger.
      Airtightness of the building
    Uncontrolled leakage through gaps must be smaller than 0.6 of the total house  volume per hour during a pressure test at 50  Pascal (both pressurised and depressurised).
Absence of thermal bridges
      All edges, corners, connections and penetrations must be planned and executed  with great care, so that thermal bridges can be avoided. Thermal bridges which  cannot be avoided must be minimised as far as possible.
|  |  |  |  | 
| Next Courses | 
PHPP Expert 
      Passive House Designer / Consultant 
      Construction Verifier 
      Site Supervisor
       read more
 read more
        
      e-learning 
    
| Events | 
iPHA Webinar "Project Spotlight: The CLT 8-floor ANMF hotel in Melbourne, Australia with heritage overlay."  | November 12, 2025 
       read more
 read more
 Passive House Open Days |
Passive House Open Days |
      7 - 9 November  2025
       read more
 read more
 24 - 25 April 2026, Essen, Germany
24 - 25 April 2026, Essen, Germany
       read more
 read more
    
| Component Database | 
 Passive House
Passive House 
      Component Database
       read more
| Projects | 
| New developments | 
 designPH
designPH
      read more
 NEW: PHPP 10 (2021)
NEW: PHPP 10 (2021) 
      read more
 Seals for Certified Passive House Components
Seals for Certified Passive House Components
      read more
      
      
    
 Passive House Classes,
Passive House Classes, 
      Classic, Plus, Premium
      read more
       EnerPHit  -
EnerPHit  -
      PHI certification  for retrofits
      read more
        
        
    
 Wall plaque
Wall plaque
      for certified Passive Houses
      read more
      
| Press releases | 
| Research & Literature | 
 Passive Houses for different climate zones
Passive Houses for different climate zones
      more
 Retrofits with Passive House components -
Retrofits with Passive House components - 
      EnerPHit Planner Handbook
      (in German)
  Passive House Retail Stores now out
Passive House Retail Stores now out
      Overview of contents
      (in German)
 
            